Flue Systems

What is a flue?

A flue is a pipe, a duct or a chimney for exhausting combustion gases from a fireplace, water heater or boiler to the outdoors. Combustion gases contain carbon monoxide and other dangerous compounds, therefore proper 'draught' and induction of replacement air is imperative.

Flue Types

The different types of flue can be described as open (conventional) flues and closed flues. Closed flues are better known as balanced flues or fanned flues and are used with room sealed units.

The draught diverter will provide an 'air gap' between the appliance and the secondary flue. This is very important as the 'pull' or suction created by the secondary flue will depend upon flue height and configuration, albeit the appliance will need to operate within its design specification which is provided by the built in components including the primary flue.

As its name suggests, an important function of the draught diverter is to allow the occasional down draught without disturbing combustion within the appliance.

This natural draught created by the draught diverter and secondary flue will pull in additional air as well as the products of combustion (exhaust gases) from the appliance. This pull can be tested by using a simple smoke test.

The secondary open flue typically continues vertically, with some lateral deviations allowable, to terminate at a suitable external point. The flue can run internally, externally or within an existing chimney (using a suitable flue liner). The greater the vertical height the greater the pull, however, the pull will be reduced depending upon the amount of lateral deviations added.


 

Balanced Flues

All room sealed appliances will have a balanced (fanned) flue. It will include an air duct to bring combustion air into the appliance. No air is taken from the space containing the appliance. Room sealed appliances are intrinsically safe as products of combustion will not normally escape into the occupied space.

As the balanced flue terminal has the flue outlet and inlet in close proximity, any draughts or gusts of wind will cancel out in the appliance, thus burner flames are not affected.

Because balanced flues are only powered by natural draught, they must be kept quite short. Usually they need only be long enough to pass through and external wall against which the appliance is installed.

3-flueing.jpg
4-flueing.jpg

Open Flues

Open flued appliances draw combustion air from its surroundings. It is vitally important that suitable ventilation is provided to the space containing the appliance. This will ensure air can enter the space from outside.

Regulation will specify what needs to be provided in each application.

An open flue usually incorporates a draught diverter near the base. The flue will consist of a 'primary flue' which is the section from the appliance heat exchanger to the draught diverter. After the draught diverter will be the secondary flue.

Most appliances incorporate draught diverters; therefore, the primary flue will only be a relatively short length of flue between the heat exchanger and the draught diverter.

Fanned Flue

Fanned flues utilise a fan to power the movement of outside air into the appliance and combustion products to external air.

This will allow much bigger lengths of flue ducts for both combustion air and exhaust air of smaller diameter and allow the inclusion of several changes of direction.

In most cases, fanned flues are concentric, meaning the combustion air duct contains the exhaust duct within it. Longer runs of duct work are possible where an individual two pipe arrangement is used to run combustion air and exhaust air separately.

Some fanned flues are also open flues, whereby taking air from the space housing the appliance. As with all open flues, the provision of adequate ventilation to supply combustion air is very important.

Quick tips

  1. The heater can be flued vertically, horizontally or any combination of both.

  2. Horizontal flueing can be used as a direct through the wall flue or extended from another internal wall.

  3. Vertical flueing is used when the water heater needs to be flued vertically through the roof.

  4. A siphon pack is required when vertical flue exceeds 1.5 metres.

  5. Rinnai Infinity internal water heaters are classified as 'room sealed' appliances. Flue systems must be installed in accordance with Rinnai Installation instructions (supplied with flue terminals), local gas fitting regulations, municipal building codes, and all other relevant statutory regulations.

  6. A full range of extensions, bends, brackets and flashings are available from Rinnai.

  7. All components for the Infinity HD and HDC range are 80mm inner diameter and 125mm outer diameter.

  8. Maximum flue length is 13m )HD) or 15m (HDC) less 2m per bend, up to a maximum of 4 bends. Additionally. the height from top of the heater to the terminal cannot exceed 9m.

  9. Only Rinai flueing systems must be used with internal water heaters, Use of non-Rinnai flueing systems will invalidate the heater warranty.

Flue sections
Universal Horizontal Non-condensing Discharged Kit
Universal Horizontal Non-condensing Kit.
45° Elbow
Vertical Roof Discharge Termination
Vent Pipe Extension
Vent Pipe Extension.png
45° Elbow.png
Vertical Roof Discharge  Termination.png